Downgrade - setting reduced charging current
Using DIP switches 4 and 5 on bank S2, the reduced charging current, which is present when the switching contact at the downgrade input is controlled, can be set. The charging current is reduced as a percentage depending on the maximum set charging current.
Configure the setting as desired.

Configurable functions:
Bank | DIP switch | Max. charging current | Reduced | Reduced | ||
---|---|---|---|---|---|---|
5 | 4 | as a % | At 16 A | 1ph at 3.7 kW | 3ph at 11 kW | |
2 | OFF | OFF | 0 % | 0 A | 0 kW | 0 kW |
ON | OFF | 25 % | 6 A | 1.4 kW | 4.1 kW | |
OFF | ON | 50 % | 8 A | 1.85 kW | 5.5 kW | |
ON | ON | 75 % | 12 A | 2.8 kW | 8.25 kW |
INFO

Too low a charging current as a result of an incorrect configuration
Upon delivery, the wallbox is set to the percentages shown in the table for the maximum charging current per phase. A charging current set to more than 0 A or less than 6 A is always set to 6 A.
These values can only be adjusted using the ENECTOR Config Tool.
You will find the ENECTOR Config Tool and instructions for how to use it in the download area > ENECTOR by going to Update.