Setting the house connection current

The maximum current per phase of the house connection must be set so that it is not overloaded when charging an electric vehicle (blackout protection).

INFO

Info

Nature and source of hazard

The maximum current which can be set per phase of the house connection depends on the fuse protection at the grid connection point (e.g. 63 A) and house connection box (e.g. 50 A downstream of grid demand meter). The lowest fuse protection (in this example 50 A) must be set here.

With a KOSTAL Smart Energy Meter and activated convenience functions, this setting for overload protection is automatically transferred.

Configure the setting as desired.

Configurable functions:

Bank

DIP switch

Charging current per phase (A)

8

7

6

2

OFF

OFF

OFF

63

OFF

OFF

ON

50

OFF

ON

OFF

40

OFF

ON

ON

35

ON

OFF

OFF

32

ON

OFF

ON

25

ON

ON

OFF

20

ON

ON

ON

16