Setting the house connection current
The maximum current per phase of the house connection must be set so that it is not overloaded when charging an electric vehicle (blackout protection).
INFO
Nature and source of hazard
The maximum current which can be set per phase of the house connection depends on the fuse protection at the grid connection point (e.g. 63 A) and house connection box (e.g. 50 A downstream of grid demand meter). The lowest fuse protection (in this example 50 A) must be set here.
With a KOSTAL Smart Energy Meter and activated convenience functions, this setting for overload protection is automatically transferred.
Configure the setting as desired.
Configurable functions:
Bank | DIP switch | Charging current per phase (A) | ||
---|---|---|---|---|
8 | 7 | 6 | ||
2 | OFF | OFF | OFF | 63 |
OFF | OFF | ON | 50 | |
OFF | ON | OFF | 40 | |
OFF | ON | ON | 35 | |
ON | OFF | OFF | 32 | |
ON | OFF | ON | 25 | |
ON | ON | OFF | 20 | |
ON | ON | ON | 16 |