PLENTICORE - load/generation measurement

Installation position – Mains connection point (standard/preferred)

Installation position – domestic consumption

Install the KOSTAL Smart Energy Meter in the domestic circuit as shown in the diagrams.

INFO

Info

The installation position of the KOSTAL Smart Energy Meter is set in the inverter.

Establish and connect the RS485 communication link between the inverter and the KOSTAL Smart Energy Meter.

Establish a LAN connection from the KOSTAL Smart Energy Meter and the inverter to the internet. Optionally, the LAN connection from the inverter can also be connected directly to the KOSTAL Smart Energy Meter (switch function).

INFO

Info

Please refer to the inverter operating instructions and the KOSTAL Smart Energy Meter installation instructions.

In this configuration, the KOSTAL Smart Energy Meter operates as a slave and sends data to the inverter.

It is not necessary to configure the inverter in the KOSTAL Smart Energy Meter, as it is pre-configured by default to use the Modbus RTU RS485 interface (A).

If you wish to make changes to the settings, carry out the following steps:

  1. Call up online interface of KOSTAL Smart Energy Meter Calling up user interface
  2. Call up Modbus configuration under Modbus settings.
  3. Select PIKO IQ/PLENTICORE from drop-down list
    Press the Save button to adopt the settings.

INFO

Info

When an inverter is selected, the predefined default values are adopted. These can be adapted if necessary.

Parameter

Value

Interface

RS485 A

Mode

Slave

Default setting

PIKO IQ/PLENTICORE

Slave address

1

Baud rate

38400

Data bits

8

Parity

None

Stop bit

2