PLENTICORE - additional scope for storage from AC energy sources

Install the KOSTAL Smart Energy Meter as shown at the grid connection point (position 2) within the domestic network.

INFO

Info

The installation position of the KOSTAL Smart Energy Meter is set in the inverter.

Establish and connect the RS485 communication line between the inverter and the KOSTAL Smart Energy Meter.

Establish a LAN connection from the KOSTAL Smart Energy Meter and the inverter to the internet. Optionally, the LAN connection from the inverter can also be connected directly to the KOSTAL Smart Energy Meter (switch function).

INFO

Info

For details, see the inverter's operating manual and the KOSTAL Smart Energy Meter's installation instructions.

In this configuration, the KOSTAL Smart Energy Meter operates as a slave and sends data to the inverter.

It is not necessary to configure the inverter in the KOSTAL Smart Energy Meter, as it is pre-configured by default to use the Modbus RTU RS485 interface (A).

In the inverter, under the menu item Battery > Battery settings > Other battery settings, the option ‘Storage of surplus AC energy from local generation’ must be enabled.

INFO

Info

For details, refer to the inverter’s operating manual. Setting on inverter only possible after logging in as an installer.

If you wish to make changes to the settings, carry out the following steps:

 

  1. Call up online interface of KOSTAL Smart Energy Meter Calling up user interface
  2. Call up Modbus configuration under Modbus settings.
  3. Select PIKO IQ/PLENTICORE from drop-down list
    Press the Save button to adopt the settings.
  4. INFO

    Info

    When an inverter is selected, the predefined default values are adopted. These can be adapted if necessary.

  5. In the inverter, under the menu item Battery > Battery Settings > Other Battery Settings, activate the option ‘Storage of surplus AC energy from local generation ’.

INFO

Info

See the inverter operating instructions for further details. Settings on the inverter can only be adjusted after logging in as an installer.

Parameter

Value

Interface

RS485 A

Mode

Slave

Default setting

PIKO IQ/PLENTICORE

Slave address

1

Baud rate

38400

Data bits

8

Parity

None

Stop bit

2