PIKO 4.2-20 / PIKO EPC - load/generation measurement

Install the KOSTAL Smart Energy Meter at the grid connection point within the domestic network, as shown in the diagram.

Establish and connect a LAN communication link between the inverter and the KOSTAL Smart Energy Meter. Optionally, the LAN connection from the inverter can also be connected directly to the KOSTAL Smart Energy Meter (switch function).

In this configuration, the KOSTAL Smart Energy Meter acts as the master and controls the inverter (e.g. for power limitation).

INFO

Info

For details, see the inverter's operating manual and the KOSTAL Smart Energy Meter's installation instructions.

Set up the inverter in the KOSTAL Smart Energy Meter. To do this, carry out the following steps:

  1. Call up online interface of KOSTAL Smart Energy Meter Calling up user interface
  2. Go to the menu item ‘System settings > Device manager’ and use the plus (+) button to add the PIKO 4.2-20 or PIKO EPC.

Parameters

Value

Series

Select PIKO FW >= 5.00

Type

Select inverter

Category

Photovoltaics

IP address

Enter the inverter’s IP address.

Maximum output power

Enter the maximum output power of the inverter. This is required if a power limit needs to be set and calculated at the grid connection point.

Open advanced settings

RS485 address

Enter the inverter’s RS485 address. This must be unique for each device (default 255).

  1. Press the Save button to adopt the settings.
  1. The inverter has been set up.