Advanced Modbus configuration
Here, further settings can be selected for the Modbus master functionality. These settings apply to all configured Modbus masters.
Transmit interval
Here, you can set an interval, at which the measurement data is to be transmitted from the KOSTAL Smart Energy Meter. The Energy Manager usually transmits its measurement data via the Modbus master as soon as it is available. If the interval is activated, the data is transmitted at a regular interval instead, regardless of when it is available. Only the current measuring values at the transmit time are ever communicated. Mean values are not produced for the interval.
Parameter | Explanation |
---|---|
Enable fixed transmit interval! | Activated Deactivated |
Set transmit interval | Select a transmit interval using the drop-down menu or enter a user-defined transmit interval in seconds at which you want the KOSTAL Smart Energy Meter to send its data. |
Averaging over transmit interval | Averaging over transmit interval switches on averaging calculations for the transmit interval. Activated Deactivated |
Register configuration
Groups of registers can be selected here, which are to be written in master mode. The system load of the KOSTAL Smart Energy Meter can therefore be reduced if all of the registers are not required. This may be necessary if lots of devices are connected to the KOSTAL Smart Energy Meter.
The arrow on the right can be used to drop down a detailed list of registers, which are contained in the respective groups.
The following registers can be activated or deactivated:
INFO
You will find information about the respective registers in the KOSTAL Smart Energy Meter- Interface Description Modbus documentation in the download area for the KOSTAL Smart Energy Meter.
Parameter | Explanation |
---|---|
Current values total | The current values for the entire system (registers 0–27) |
Current values phases | The current values itemised by phase (registers 40-145) |
Energy values total | The energy values for the entire system (registers 512-551) |
Energy values phases | The energy values itemised by phase (registers 592-791) |