Wallbox charging control

To gain a better understanding of how the charging process works with and without a battery, and when prioritising the wallbox or the battery, please refer to the tables below for a brief explanation.

If ‘Do not use battery’ is selected, the battery will still be used under certain conditions to minimise the vehicle constantly switching on and off.

Furthermore, in Solar Pure Mode, the battery is used when the solar panels are shaded by clouds, again to prevent the charging process from being constantly interrupted.

Glossary

Term

Explanation

PV surplus

PV surplus is the sum of PV generation minus household consumption.

Minimum charging power

Depends on the minimum charging current and the number of phases used.

The example calculation shows the minimum charging power based on the currently set minimum charging current for both single-phase and three-phase charging processes.

The minimum charging current for three-phase vehicles is usually 6A per phase, i.e. 18A for all three phases, which amounts to just under 4.2 kW.

The minimum charging current for single-phase vehicles is usually 6A per phase, i.e. just under 1.4 kW.

Cloud cover hysteresis

This function serves to smooth out the control process in the event of changeable weather (e.g. cloud cover) and fluctuating PV output, and to avoid unnecessary interruptions to charging.

When there is a drop in PV output, a hysteresis period is initiated. Wallbox charging processes continue at full power. Once the hysteresis period has elapsed, the charging power is reduced, an automatic phase switch is carried out, or the charging process is paused if the PV surplus is insufficient for the current charging power.

The duration of the hysteresis is 5 minutes.

If the PV surplus required for the charging process is exceeded during the hysteresis period, the timer is stopped and the hysteresis is terminated.

If the required power level is again fallen below, a new hysteresis cycle begins.

If, during cloud cover hysteresis, the timer for automatic phase switching expires, the system switches to single-phase charging without waiting for the full 5 minutes to elapse.

Shut-off hysteresis

If, after the cloud cover hysteresis has elapsed, there is insufficient surplus PV power to continue the charging process at the minimum charging power, the charging process is switched off. The charging process will not be switched on again until at least the 8-minute switch-off hysteresis has elapsed. This hysteresis can be terminated prematurely by manually switching the charging modes.

Initialisation (probing)

During the initialisation of the charging process, the minimum and maximum charging currents for the car and the wallbox are determined. These depend on the connected vehicle and the state of charge (SoC) of the vehicle battery, as well as on environmental conditions (for example, temperatures below 0°C or above 40°C).

To determine the maximum power, this must be supplied briefly (e.g. 11 kW for three-phase charging), even if it is not available in the current charging mode (e.g. insufficient surplus PV). This may result in the home battery being briefly discharged for the probing process.

Automatic phase switching

When this function is enabled, the number of phases with which the wallbox can charge is automatically switched depending on the set charging mode and the available surplus PV.

The starting point is a three-phase charging process with sufficient PV surplus.

If charging processes are restricted due to a lack of available PV power, this is first applied to the current to the car. If the current were to fall below the minimum charging current, the cloud-pass hysteresis is initiated and, once this period has elapsed, a phase switch to single-phase charging takes place. After the charging process has been switched off, the phase changeover to single-phase is initiated after a 2-minute waiting period . This is followed by a probe test, and if there is sufficient PV power, charging continues in single-phase mode.

Every 15 minutes, the system checks whether, based on the current PV surplus, a phase change from single-phase to three-phase or from three-phase to single-phase should take place.

If, when the timer expires, a phase change from three-phase to single-phase is due to take place and a cloud cover hysteresis is active, the phase change takes place immediately.

If a cloud-passing hysteresis period expires, a phase change from three-phase to single-phase is also carried out immediately, independently of the 15-minute timer for automatic phase switching.

For a switchover from single-phase to three-phase, there must be at least a PV surplus of

minimum charging power plus 7 per cent . As a rule, this amounts to 4.5 kW.

Charge control in Solar Pure Mode

Surplus

Wallbox Prio

Allow use of home battery

Wallbox Priority

Do not allow use of home battery

Home battery priority

Surplus > Minimum charging power

  • The wallbox charges using surplus energy.
  • The home battery charges using additional surplus power, if available.
  • No grid draw.
  • The wallbox charges when the home battery is full or using additional surplus energy, if available.
  • The home battery charges using surplus energy.
  • No grid draw.

Surplus < minimum charging power

  • The wallbox charges at iMin. (1)(3)
  • The home battery discharges to cover household consumption and the charging process.
  • No power drawn from the grid.
  • The wallbox is not charging.
  • Home battery charges using surplus energy.
  • No power drawn from the grid.

No surplus

  • Wallbox is charging at iMin. (1)(3)
  • The home battery is discharging to cover household consumption and the charging process.
  • No grid draw.
  • Wallbox is not charging.
  • Home battery discharges to cover household consumption not covered by PV.
  • No grid draw.

Probing and hysteresis

  • The home battery is discharged for probing and hysteresis.
  • No power is drawn from the grid.
  • The home battery is not discharged for probing and hysteresis.
  • Power may be drawn from the mains.

Charge control in Solar Plus mode

In Solar Plus mode, the minimum charging power can be set. The description in this mode always refers to the set minimum charging power.

Surplus

Wallbox Prio

Allow use of home battery

Wallbox Priority

Do not allow use of home battery

Home battery priority

Surplus > Minimum charging power

  • The wallbox charges using surplus energy.
  • The home battery charges using additional surplus energy, if available.
  • No grid draw.
  • The wallbox charges when the home battery is full or using additional surplus energy, if available.
  • The home battery charges using surplus energy.
  • No grid draw.

0 < surplus < minimum charging power

 

Surplus > minimum charging power * slider

  • The Wallbox charges at iMin.
  • The home battery discharges and covers the home’s consumption.
  • Grid power is drawn.
  • The wallbox charges at iMin when the home battery is full, or with any additional surplus, if available.
  • The home battery charges using surplus energy.
  • Grid draw may occur.

0 < surplus < minimum charging power

 

Surplus < minimum charging power * slider

  • The Wallbox charges at iMin. (1)(3)
  • The home battery discharges to cover household consumption and the charging process.
  • Power may be drawn from the mains.
  • The wallbox is not charging.
  • Home battery charges using surplus energy.
  • No power is drawn from the grid.

No surplus

  • Wallbox is charging at iMin. (1)(3)
  • The home battery is discharging to cover household consumption and the charging process.
  • Power may be drawn from the grid.
  • The wallbox does not charge unless the slider is set to 0.
  • The home battery discharges to cover household consumption not covered by PV.
  • Power may be drawn from the grid.

Probing and hysteresis

  • The home battery may discharge for probing and hysteresis.
  • Power may be drawn from the grid.
  • The home battery must not discharge for probing and hysteresis.
  • Power may be drawn from the mains.

Charge control in Power Mode (mains charging)

Surplus

Wallbox Priority

Allow use of domestic battery

Wallbox Priority

Do not allow use of home battery

Home battery priority

Surplus available

  • Wallbox charges at iMax.
  • Home battery charges using any additional surplus, if available.
  • The home battery discharges to supply the wallbox if the surplus is insufficient for iMax.
  • Power may be drawn from the grid if the home battery is empty.
  • The wallbox charges using iMax.
  • The home battery charges using any additional surplus energy, if available.
  • The home battery does not discharge to the wallbox.
  • Power may be drawn from the mains.
  • The wallbox charges using iMax.
  • Grid draw is reduced if the home battery is full or if additional surplus energy is available.
  • The home battery charges using surplus energy. (2)
  • Power may be drawn from the mains.

No surplus available

  • The Wallbox charges at iMax.
  • The home battery discharges to supply the wallbox.
  • The home battery discharges to cover household consumption not covered by PV.
  • Power may be drawn from the grid.
  • The wallbox is charging at iMax with 100% grid draw.
  • The home battery discharges to cover household consumption not covered by the solar panels.
  • Grid draw occurs.

 

(1) It may happen that the wallbox charges continuously at a rate higher than iMin, as the home battery attempts to reduce grid draw to 0 and is recognised by the control system as surplus PV.

(2) The surplus PV is not used to charge the home battery, as the home battery cannot be charged whilst there is net draw.

(3) When switching to ‘Wallbox Priority’ mode , if the PV surplus is insufficient, the shortfall is not initially covered by the battery. However, existing charging processes are balanced accordingly.