Data logger

1

Select resolution

2

Select measurement source

3

Measurement type

4

Select sensors

5

Date selection

6

Graph

The data logger enables the storage of all energy and power readings from all sensors, auxiliary devices and the main unit at intervals of 1 minute, 15 minutes, 1 hour or 1 day.

In addition, the minimum, maximum and average values for the power readings are calculated and stored for the respective intervals.

Resolution

Resolutions of 15 minutes, 1 hour and 1 day are available for the graph.

These can be displayed according to the storage duration:

More detailed resolutions of 1 minute and 1 second are only available for CSV export. However, data can only be displayed if measurements are already available for the selected time period.

Data source

In addition to connected devices, such as sensors, smart meters are also available as data sources. By default, data for smart meters is displayed. Clicking the drop-down menu lists the available measurement sources. Clicking a measurement source adds the corresponding data to the graph. The measurement source also appears as an entry in the drop-down menu.

By clicking on the ‘X’ at the end of the entry, any measurement source currently shown in the graph can be removed. Up to 3 measurement sources can be selected. If 3 measurement sources are selected, no further sources can be chosen. A new measurement source can only be selected after at least one of the 3 measurement sources has been removed.

Measured variable and measurement type

Depending on the selection of measurement sources, the corresponding measured variables are displayed. The total number of measured variables is calculated; that is, if a measured variable is not available for a selected measurement source, no trend line is displayed in the graph for that source.

If only one measurement source is selected, all three measurement types are displayed:

If more than one measurement source is selected, the relevant measurement type can be specified.

For energy-type measured variables, no selection of measurement types is available, as only the total is displayed here.

Manual export

The manual export function allows the stored data from all available sources to be exported.

Resolutions

The following resolutions can be selected:

There are two drop-down menus for configuring the start and end dates of the export. Clicking on a drop-down menu opens a calendar. Days that are not available for the selected resolution are shown in pale colour. For the 1-minute, 15-minute and 1-hour resolutions, a specific time can also be selected. Once the relevant selection has been made, the ‘Export’ button can be used to start downloading a ZIP archive. Depending on the configuration in the settings, this will contain either one CSV file per measurement source or a single large CSV file containing all measurement sources.

If there are a large number of connected sensors, there may be longer waiting times (up to several minutes) whilst the data is being exported. The export will abort if the waiting time exceeds 15 minutes.

Only one export process can be active at a time. Further requests will be rejected with an error message if an export process is already running. Manual exports are also not possible whilst an automatic export is in progress.

Settings

The settings can be accessed by clicking on the button with the cog icon.

 

General settings

Data logging can be enabled or disabled via ‘Record Measurements’ . If data logging is disabled, data export via FTP and email will also be stopped.

The ‘1-second data’ function can also be switched on or off here. This function places an additional load on the device’s RAM, particularly when there are many data sources. Therefore, this function should only be activated when necessary .

Storage status

The memory usage is displayed here as a percentage. The storage duration describes how long measured values are stored according to their resolution:

 

Export settings

Here you can configure the export format and the automatic, scheduled export of data.

Legacy format

When the legacy format is used, the values from all data sources are exported into a single CSV file. If the compression option is also selected, this file is packed into a ZIP archive.

The legacy format setting applies to both manual export and automatic export via email and FTP. The compression option applies only to automatic export. When exporting manually, a ZIP archive is always generated.

Note: The legacy format has the restriction that only values from Smart Meters and Sensorbars sensors are exported.

Resolution and transmission interval

Here, you can select the interval and resolution of the exported data. Depending on the selected transmission interval, a specific resolution can be chosen:

In addition, a start date can be selected for when the automatic export is to begin.

FTP export settings

FTP export can be enabled as soon as an FTP server has been configured in the device settings . As an additional option, a subdirectory path can be specified.

Email export settings