Modbus Mapping
Modbus mapping displays an overview of all Modbus addresses assigned to applications and devices.
Static Modbus mapping
Display of the static register blocks for the applications in use.
Dynamic Modbus mapping
Dynamic register blocks are created automatically. Their exact start and end addresses are displayed in the table. New register blocks are always created at the lowest possible address. Register blocks for devices that cannot currently be accessed (e.g. due to a connection error) are retained in the configuration. These devices are marked with the status ‘Offline’ in the overview table.
The ‘Defragment’ button can be used to defragment the register area. In the process, devices with the ‘Offline’ status are removed from the table. The arrangement of the register blocks is changed so that register blocks of the same type are placed directly one after the other and there are no gaps of unused registers between two register blocks.
Defragmentation therefore alters the Modbus interface within the area of the dynamic register blocks that is addressed by external devices. This may result in the devices being assigned a different address range.