Settings in the KOSTAL Smart Energy Meter
RS485 interface
By default, no changes have to be made to the RS485 interfaces. These arrive preconfigured.
The following devices can be connected to the RS485 interfaces:
- RS485 (A): PLENTICORE plus / PLENTICORE BI
- RS485 (B): PIKO MP plus
If changes are to be made to the settings, perform the following steps:
- Call up online interface of KOSTAL Smart Energy Meter Calling up user interface
- Call up Modbus configuration under Modbus settings.
- Select PIKO IQ/PLENTICORE from drop-down list
Press the Save button to adopt the settings.
INFO
When an inverter is selected, the predefined default values are adopted. These can be adapted if necessary.
Parameter | Value |
---|---|
Interface | RS485 A |
Mode | Slave |
Presetting | PIKO IQ/PLENTICORE |
Slave address | 1 |
Baud rate | 38400 |
Data bits | 8 |
Parity | None |
Stop bit | 2 |