Cable specification

AC grid connection

Select the conductor cross-section according to the rated output current and the type of routing.

INFO

Info

For outdoor installation, use UV-resistant cable. Alternatively, lay the cable protected from solar radiation.

The 4-wire AC connection (3L/PE without N) is only possible in symmetrical networks.

Take into account necessary reduction factors for ambient temperature and accumulation (when laying several cables without spacing).

Example: Ambient temperature 40 °C: Reduction factor 0.87 (according to DIN VDE 0100-520 / HD 60364-5-52).

AC cable specifications (grid connection)

Connection method

4-wire (3L/PE without N) or 5-wire (3L/N/PE)

Cable length

max. 200 m

Material

Copper/aluminium

Wire cross-section

Copper: 70 – 240 mm²/aluminium: 95 – 240 mm²

Cable diameter

24 – 69 mm

Wire diameter

14 – 32 mm

Additional PE connection

≥ 35 mm² (wire cross-section x 0.5)

 

DC cable specifications (PV connection)

Cable type

Solar cable e.g. PV1-F

Wire cross-section

4 – 6 mm²

Cable diameter

6 – 8 mm