Cable specification
AC grid connection
Select the conductor cross-section according to the rated output current and the type of routing.
INFO

For outdoor installation, use UV-resistant cable. Alternatively, lay the cable protected from solar radiation.
The 4-wire AC connection (3L/PE without N) is only possible in symmetrical networks.
Take into account necessary reduction factors for ambient temperature and accumulation (when laying several cables without spacing).
Example: Ambient temperature 40 °C: Reduction factor 0.87 (according to DIN VDE 0100-520 / HD 60364-5-52).
AC cable specifications (grid connection) | |
---|---|
Connection method | 4-wire (3L/PE without N) or 5-wire (3L/N/PE) |
Cable length | max. 200 m |
Material | Copper/aluminium |
Wire cross-section | Copper: 70 – 240 mm²/aluminium: 95 – 240 mm² |
Cable diameter | 24 – 69 mm |
Wire diameter | 14 – 32 mm |
Additional PE connection | ≥ 35 mm² (wire cross-section x 0.5) |
DC cable specifications (PV connection) | |
---|---|
Cable type | Solar cable e.g. PV1-F |
Wire cross-section | 4 – 6 mm² |
Cable diameter | 6 – 8 mm |