Selecting PV inputs
If the inverter's DC inputs are not fully occupied, distribute the input assignment in accordance with the following tables: Make sure that the maximum input current (IDCmax) per MPPT and the maximum DC current per DC input (IStringmax) are not exceeded in the process:
INFO

Only connect PV modules of the same type to an MPP tracker, i.e.:
- same manufacturer,
- same type,
- same performance,
- same size.
Maximum input current
UDCstart | UDCmax | IDCmax per MPP tracker | IStringmax |
---|---|---|---|
≤ 250 V | ≤ 1100 V | MPPT 1: 40 A MPPT 2: 40 A MPPT 3: 40 A MPPT 4: 32 A MPPT 5: 32 A MPPT 6: 32 A MPPT 7: 32 A MPPT 8: 32 A | DC 1-2: ≤ 20 A DC 3-4: ≤ 20 A DC 5-6: ≤ 20 A DC 7-8: ≤ 20 A* DC 9-10: ≤ 20 A* DC 11-12: ≤ 20 A* DC 13-14: ≤ 20 A* DC 15-16: ≤ 20 A* |
* With 2 DC strings connected, IStringmax ≤ 16 A.
DC connection assignment PIKO CI 100
Connected PV strings | MPP trackers | |||||||
---|---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4* | 5* | 6* | 7* | 8* | |
Used DC input | ||||||||
1 | 1 |
|
|
|
|
|
|
|
2 | 1 | 3 |
|
|
|
|
|
|
3 | 1 | 3 | 5 |
|
|
|
|
|
4 | 1 | 3 | 5 | 7 |
|
|
|
|
5 | 1 | 3 | 5 | 7 | 9 |
|
|
|
6 | 1 | 3 | 5 | 7 | 9 | 11 |
|
|
7 | 1 | 3 | 5 | 7 | 9 | 11 | 13 |
|
8 | 1 | 3 | 5 | 7 | 9 | 11 | 13 | 15 |
9 | 1, 2 | 3 | 5 | 7 | 9 | 11 | 13 | 15 |
10 | 1, 2 | 3, 4 | 5 | 7 | 9 | 11 | 13 | 15 |
11 | 1, 2 | 3, 4 | 5, 6 | 7 | 9 | 11 | 13 | 15 |
12 | 1, 2 | 3, 4 | 5, 6 | 7, 8 | 9 | 11 | 13 | 15 |
13 | 1, 2 | 3, 4 | 5, 6 | 7, 8 | 9, 10 | 11 | 13 | 15 |
14 | 1, 2 | 3, 4 | 5, 6 | 7, 8 | 9, 10 | 11, 12 | 13 | 15 |
15 | 1, 2 | 3, 4 | 5, 6 | 7, 8 | 9, 10 | 11, 12 | 13, 14 | 15 |
16 | 1, 2 | 3, 4 | 5, 6 | 7, 8 | 9, 10 | 11, 12 | 13, 14 | 15, 16 |
(*) With 2 DC strings connected, IStringmax ≤ 16 A.