Solar module connections

DANGER

danger

Risk of death due to electrical shock and discharge!

The PV generators/cables may be live as soon as they are exposed to light.

WARNING

warning

Serious burns due to arcs on the DC side!

During operation, dangerous arcs can occur when pulling or plugging the DC connections.

Before connecting the DC connectors, de-energise the DC side. DC switches must be in the OFF position.

WARNING

warning

Risk of fire due to improper installation!

Incorrectly fitted plugs and sockets may heat up and cause a fire.

During installation, be sure to follow the manufacturer's requirements and manual. Properly mount plugs and sockets.

POSSIBLE DAMAGE

Schaden_moeglich

Risk of damage to the inverter due to PV modules connected with the wrong polarity

PV modules connected with the wrong polarity may cause thermal damage to the inverter.

  • Measure the DC cables of the PV modules and connect to inverter with the correct polarity.
  • Comply with the maximum input current per string for the inverter as stated in the technical data.
  • The maximum input current must not be exceeded, even when using Y or T plugs.

Please note the following points before connecting the PV modules:

UDCstart

UDCmax

250

1100

Failure to observe these requirements will render any warranty, guarantee or other liability offered by the manufacturer null and void.