Other settings

Parameter

Explanation

Isolated network detection

Activate/deactivate isolated network detection.

Ensures that the inverter does not switch on or off in the event of supply voltage errors.

Residual current monitoring

Activate/deactivate residual current monitoring.

When the function is enabled, the inverter detects the array fault current.

Shadow management

If PV strings are in partial shading, the PV string affected no longer achieves its optimum performance. If shadow management is activated, the inverter adapts the MPP tracker in such a way that it can operate at maximum possible performance.

Shadow management interval time (s)

Set the interval of the MPP tracker sampling rate

Insulation resistance (kOhm)

If the value established for insulation resistance is less than the preset value, the inverter is not connected to the grid

Leakage current limit (mA)

Limit value for leakage current detection. If the value established is higher than the preset value, the inverter will shut down.

Limit for unbalanced voltage (%)

Setting the threshold value for DC voltage asymmetry

Dynamic grid support (FRT)

Dynamic grid support (FRT = Fault Ride Through)

 

Positive sequence K factor

Settings for uninterrupted cycling through grid faults

FRT (Fault Ride Through)

Negative sequence K factor

Monitoring of supply voltage

Undervoltage ride through (V) UVRT

Overvoltage ride through (V) OVRT

Grid support mode

Limited grid support (%)

Irregular voltage change (%)

Overvoltage protection monitoring

Activate/deactivate monitoring of the internal overvoltage protection modules (SPD - Surge Protective Device).

AFCI function

Activate arc detection.

Reset arc errors

Reset arc errors. This should only be done if the cause has been established.

Arc error sensitivity adjustment value

Adjust the sensitivity (default value: 40).

Arc detection adjustment value

Adjust the value for arc detection or use the default value (default value: 16)

Current arc intensity adjustment value

Adjust the value for current arc intensity or use the default value (default value: 800)

Average arc intensity adjustment value

Adjust the value for average arc intensity or use the default value (default value: 200)