Cable specification

Grid connection AC

Select the conductor cross-section according to the rated output current and the type of routing.

INFO

Info

For outdoor installation, use UV-resistant cable. Alternatively, lay the cable protected from solar radiation.

The 4-wire AC connection (3L/PE without N) is only possible in symmetrical networks.

Take into account necessary reduction factors for ambient temperature and accumulation (when laying several cables without spacing).

Example: Ambient temperature 40 °C: Reduction factor 0.87 (according to DIN VDE 0100-520 / HD 60364-5-52).

Cable type

Cable length

Copper conductor

4-wire (3L/PE without N) or

5-wire (3L/N/PE)

max. 200 m

 

PIKO CI

Wire cross-section

Cable diameter

30

10 - 25 mm²

24 - 32 mm

50 / 60

30 - 50 mm²

25 - 40 mm

 

Additional PE connection

PIKO CI

Wire cross-section

30

≥ 16 mm²

50 / 60

≥ 35 mm²

 

DC PV connections

Cable type

Wire cross-section

Cable diameter

Solar cable

e.g. PV1-F

4 - 6 mm²

6 - 8 mm