Selecting PV inputs
If the inverter's DC inputs are not fully occupied, distribute the input assignment in accordance with the following tables: Make sure that the maximum input current (IDCmax) per MPPT and the maximum DC current per DC input (IStringmax) are not exceeded in the process:
INFO

Only connect PV modules of the same type to an MPP tracker, i.e.:
- same manufacturer,
- same type,
- same performance,
- same size.
Maximum input current
PIKO CI G2 | UDCstart | UDCmax | IDCmax per MPP tracker | IStringmax |
---|---|---|---|---|
30 | ≤200 V | ≤1100 V | MPPT 1: 40 A MPPT 2: 32 A MPPT 3: 32 A | DC 1-2: ≤ 20 A DC 3-4: ≤ 20 A DC 5-6: ≤ 20 A
|
50 | ≤200 V | ≤1100 V | MPPT 1: 40 A MPPT 2: 32 A MPPT 3: 32 A MPPT 4: 32 A | DC 1-2: ≤ 20 A DC 3-4: ≤ 20 A DC 5-6: ≤ 20 A DC 7-8: ≤ 20 A |
DC connection assignment
PIKO CI G2 | Connected PV strings | MPP trackers | |||
---|---|---|---|---|---|
1 | 2 | 3 | 4 | ||
Used DC input | |||||
30 | 1 | 1 |
|
| -- |
2 | 1 | 2 |
| --- | |
3 | 1 | 2 | 3 | -- | |
4 | 1, 2 | 3 | 4 | -- | |
5 | 1, 2 | 3, 4 | 5 | -- | |
6 | 1, 2 | 3, 4 | 5, 6 | -- | |
50 | 1 | 1 |
|
|
|
2 | 1 | 2 |
|
| |
3 | 1 | 2 | 3 |
| |
4 | 1 | 2 | 3 | 4 | |
5 | 1, 2 | 3 | 4 | 5 | |
6 | 1, 2 | 3, 4 | 5 | 6 | |
7 | 1, 2 | 3, 4 | 5, 6 | 7 | |
8 | 1, 2 | 3, 4 | 5, 6 | 7, 8 |