Selecting PV inputs

If the inverter's DC inputs are not fully occupied, distribute the input assignment in accordance with the following tables: Make sure that the maximum input current (IDCmax) per MPPT and the maximum DC current per DC input (IStringmax) are not exceeded in the process:

INFO

Info

Only connect PV modules of the same type to an MPP tracker, i.e.:

  • same manufacturer,
  • same type,
  • same performance,
  • same size.

 

Maximum input current

PIKO CI G2

UDCstart

UDCmax

IDCmax per MPP tracker

IStringmax

30

200 V

1100 V

MPPT 1: 40 A

MPPT 2: 32 A

MPPT 3: 32 A

DC 1-2: ≤ 20 A

DC 3-4: ≤ 20 A

DC 5-6: ≤ 20 A

 

50

200 V

1100 V

MPPT 1: 40 A

MPPT 2: 32 A

MPPT 3: 32 A

MPPT 4: 32 A

DC 1-2: ≤ 20 A

DC 3-4: ≤ 20 A

DC 5-6: ≤ 20 A

DC 7-8: ≤ 20 A

DC connection assignment

PIKO CI G2

Connected PV strings

MPP trackers

1

2

3

4

Used DC input

30

1

1

 

 

--

2

1

2

 

---

3

1

2

3

--

4

1, 2

3

4

--

5

1, 2

3, 4

5

--

6

1, 2

3, 4

5, 6

--

50

1

1

 

 

 

2

1

2

 

 

3

1

2

3

 

4

1

2

3

4

5

1, 2

3

4

5

6

1, 2

3, 4

5

6

7

1, 2

3, 4

5, 6

7

8

1, 2

3, 4

5, 6

7, 8