Technical data
Subject to technical changes. Errors excepted.
You can find current information at www.kostal-solar-electric.com.
Power class
Battery inverters | Unit | PLENTICORE BI G2 | |
---|---|---|---|
Power class | 5.5/26 | 10/26 |
Input side (DC)
PLENTICORE BI G2 | Unit | 5.5/26 | 10/26 |
---|---|---|---|
Battery input min. working voltage range (Udc,workbatmin) | V | 120 | |
Battery input max. working voltage range (Udc,workbatmax) | V | 650 | |
Battery input max. charge/discharge current | A | 26/26 | |
Number of DC inputs | 1 |
Output side (AC)
PLENTICORE BI G2 | Unit | 5.5/26 | 10/26 |
---|---|---|---|
Rated power, cos φ = 1 (Pac,r) | kW | 5.5 | 10 |
Output apparent power (Sac,nom, Sac,max) | kVA | 5.5 | 10 |
Min. output voltage (Uac,min) | V | 320 | |
Max. output voltage (Uac,max) | V | 500 | |
Rated output current (lac,r) | A | 7.94 | 14.43 |
Max. output current (Iac,max) | A | 8.82 | 16.04 |
Inrush current (IInrush) | A | 2.46 | 6.72 |
Short-circuit current (peak/RMS) | A | 12.5/8.8 | 22.8/16.1 |
Number of feed-in phases | 3 | ||
Grid connection | 3N~, 230/400 V, 50 Hz | ||
Rated frequency (fr) | Hz | 50 | |
Grid frequency (fmin - fmax) | Hz | 47/53 | |
Setting range for the power factor (cos φAC,r) | 0.8…1…0.8 | ||
Power factor at rated power (cos φAC,r) | 1 | ||
THD | % | 3 |
Unit characteristics
PLENTICORE BI G2 | Unit | 5.5/26 | 10/26 |
---|---|---|---|
Standby | W | 7.9 |
Efficiency
PLENTICORE BI G2 | Unit | 5.5/26 | 10/26 |
---|---|---|---|
Max. efficiency BAT2AC | % | 96.6 | 96.7 |
Max. efficiency AC2BAT | % | 96.8 |
System data
PLENTICORE BI G2 | Unit | 5.5/26 | 10/26 |
---|---|---|---|
Topology: Without galvanic isolation – transformerless | Yes | ||
Protection class in accordance with IEC 60529 | IP 65 | ||
Protective class according to IEC 62103 | I | ||
Overvoltage category according to IEC 60664-1 on output side (grid connection) | III | ||
Degree of contamination | 4 | ||
Environmental category (indoor installation) | Yes | ||
UV resistance | Yes | ||
AC cable diameter (min-max) | mm | 8…17 | |
AC cable cross-section (min-max) | mm² | 1.5…6 | 4…6 |
Battery cable cross-section (min-max) | mm² | 6 | |
Torque of screws in terminal compartment | Nm | 2 | |
Torque of screws in cover | Nm | 1.5 | |
Max. fuse protection on output side (AC) IEC 60898-1 | A | B16 / C16 | B25 / C25 |
Compatibility with external residual current protection devices | Type A RCD | ||
Internal operator protection in accordance with EN 62109-2 | Yes | ||
Independent disconnection device according to VDE V 0126-1-1 | Yes | ||
Electronic DC disconnection device integrated | Yes | ||
Reverse polarity protection, DC side | Yes | ||
Height/width/depth | mm | 563 / 405 / 233 | |
Weight | kg | 17.9 (39.46) | 19.9 (43.87) |
Cooling principle – regulated fans | Yes | ||
Max. air throughput | m³/h | 184 | |
Noise emission (typical) | dB(A) | 39 | |
Ambient temperature | °C | -20…60 | |
Max. operating altitude above sea level | m | 2000 | |
Relative humidity | % | 4…100 | |
Connection technology, DC side | SUNCLIX plug | ||
Connection technology, AC side | Spring-type terminal strip | ||
Connection technology, COM | Push-in terminals |
Interfaces
PLENTICORE BI G2 | Unit | 5.5/26 | 10/26 |
---|---|---|---|
Ethernet (RJ45/100 Mbit/s) | 2 | ||
Wi-Fi (2.4 GHz [IEEE 802.11 b/g/n]) | Yes | ||
RS485 | 1 | ||
Energy meter connection for collecting energy data (Modbus RTU) | 1 | ||
Digital inputs | Yes (e.g. for external battery control, OVP evaluation) | ||
Digital outputs | 4 (24 V, 100 mA) | ||
Webserver (user interface) | Yes |
Directives / Certification
Directives / Certification |
---|
CE, GS, CEI 0-21, C10/11, EN 62109-1, EN 62109-2, EN 60529, EN 50438*, EN 50549-1*, NA/EEA, G98, G99, EIFS2018, IEC 61727, IEC 62116, RD 1699, RD 647, RFG (EU 2016/631), TF3.3.1, TOR generators, UNE 206006, UNE 206007-1, VDE 0126-1-1, VDE-AR-N 4100/4105, VJV2018 (* does not apply to all national annexes) |
Overvoltage category III (AC output): The device is suitable for permanent connection in the grid distribution behind the meter and the line protection fuse. If the connection cable travels outdoors over long distances, overvoltage protection devices may be necessary.
Degree of contamination 4: Contamination results in continuous conductivity, e.g. due to conductive dust, rain or snow; indoors or outdoors.
Automatic disconnection device in accordance with VDE V 0126-1-1, for Austria: The inverter is equipped "with automatic disconnection device in accordance with ÖVE/ÖNORM E 8001-4-712".
Noise emission: Measured under rated output at an ambient temperature of 23 °C. If a string connection is unfavourable or there is a higher ambient temperature, the noise emission may be up to 48 dB(A).