Installation
Selecting the installation site.
IMPORTANT INFORMATION
Loss of warranty due to incorrect installation
Observe these instructions when selecting the installation site. Failure to observe these instructions may limit guarantee claims or render them fully null and void.
- Be absolutely sure to maintain the clearance around the inverter in order that the inverter remains cool.
- To mount the inverter, use the wall mount and fastening screws that are suitable for the substrate.
|
Protect inverter against exposure to direct sunlight. |
|
Protect inverter from rain and splash water. |
|
Protect inverter from falling parts which could enter the inverter's ventilation openings. |
|
Protect the inverter against dust, contamination and ammonia gases. Rooms and areas containing livestock are not permitted as installation sites. |
|
Mount inverter on a stable installation surface that can safely bear the weight. Plasterboard walls and wood planking are not permitted. |
|
Mount inverter on a non-flammable installation surface.
|
|
A sufficient safety distance from flammable materials and potentially explosive areas in the vicinity must be ensured. |
|
Inverters can cause noise when in operation. Install inverter in such a way that people are not disturbed by operation noises. |
|
Mount inverters on vertical installation surfaces. |
|
Maintain minimum distances and the necessary clearance. |
|
Inverter may only be installed up to an altitude of 2000 m. |
|
The ambient temperature must be between -20 °C and +60 °C. |
|
The air humidity must be between 4% and 100% (condensing). |
|
Install inverters so that they are not accessible to children. |
|
Inverters must be easily accessible and the display clearly legible. |