Connecting ripple control receiver

DANGER

danger

Risk of death due to electrical shock and discharge!

  • De-energise device and secure against being switched on again.

Perform the following steps:

  1. Switch the DC switch on the inverter to OFF.
  2. De-energise the house grid and secure it against being switched back on.
  3. Fit ripple control receiver in control cabinet or power distributor.
  4. Correctly route the communication cable from the inverter to the control cabinet and connect to the ripple control receiver following the wiring diagram provided by the manufacturer.
  5. Connect communication cable in inverter to terminal for ripple control receiver (torque: 0.2 Nm).
  6. Once the inverter has undergone initial commissioning, the ripple control receiver must be configured in the Webserver. Forwarding of the ripple control receiver’s signals (distribution of broadcast control signals) to other inverters in the same house grid can also be activated.
  1. The ripple control receiver is connected.