Activation of battery input

If DC input 3 on the inverter has not been activated for battery use, the battery activation code must be entered in the inverter so that it can be activated. There are three ways of doing this.

INFO

Info

Be sure to use a valid activation code. If the details entered are incorrect, the inverter will be blocked after the 5th attempt and can only be enabled again by completely disconnecting the inverter from the AC and DC voltage supply.

Inputting code upon initial commissioning:

  1. During initial commissioning, the commissioning wizard asks for the battery activation code under Extra options. In this case, enter the 10-digit activation code for the battery and confirm it.
  2. Once this has been acknowledged, DC input 3 can be used to connect a battery storage unit.
  1. Activation is complete.

Inputting code via Webserver:

After initial commissioning, the battery activation code can be entered via the Webserver.

  1. Calling up Webserver
  2. Go to Service menu > Extra options > Release new option.
  3. Enter the 10-digit battery activation code and confirm.
  4. The operating mode must then be activated by going to Service menu > Operating mode > Change operating mode to add the battery to the inverter.
  1. Activation is complete.

Inputting code via inverter menu:

  1. After initial commissioning, the battery activation code can be entered in the inverter via the following menu item:
  2. Settings > Extra options > Activate options
  3. Enter the 10-digit battery activation code and confirm.
  4. The operating mode must then be activated by going to Service menu > Operating mode > Change operating mode to add the battery to the inverter.
  1. Activation is complete.