Limitations in backup mode

The inverter is a hybrid inverter that is designed for optimal use in parallel grid operation.

If there is a grid failure, the inverter can establish its own 3-phase backup power network using an emergency generation mode, also called backup mode.

The inverter is not designed to be used permanently as a microgrid inverter. The maximum number of operating hours in backup mode is 5000 hours. The warranty for the device then expires because the load in backup mode is higher than in grid mode.

Consumers in backup mode

Be aware that not all consumers in the house grid can be supplied with energy, because the power from the battery and PV modules is not sufficient at all times. Therefore, in backup mode, it makes sense to only supply certain consumers with energy.

Compatible backup switches make it possible to divide up the supply to the house. All consumers that are not required during a grid failure are connected to the grid mode branch. Consumers that should continue to be supplied during backup mode go in the backup mode branch.

If an overload occurs in the house grid because there are too many consumers in backup mode or when a backup power network is being established, the inverter tries to establish a backup power network three times before shutting down. A message on the inverter display indicates that this has happened. If this occurs, reduce the consumers and acknowledge the message on the inverter display. The inverter then tries to establish a backup power network again.

1

PLENTICORE G3

2

KOSTAL BackUp Switch (manual switch)

3

Mains operation

4

Backup mode

5

Consumers in grid mode

6

Consumers in backup mode

Be aware of the following points: