Limitations in backup mode

The inverter is a hybrid inverter designed for optimum use in grid-parallel operation.

In the event of a mains failure, the inverter can establish its own emergency power supply network via emergency power mode, also known as backup mode.

The inverter is not designed for continuous use as an off-grid inverter. The maximum number of operating hours in backup mode is 5,000 hours. After this, the warranty for the unit will lapse, as the load in backup mode is higher than in grid-connected mode.

Consumers in backup mode

Be aware that not all consumers in the house grid can be supplied with energy, because the power from the battery and PV modules is not sufficient at all times. Therefore, in backup mode, it makes sense to only supply certain consumers with energy.

Compatible backup switches make it possible to divide up the supply to the house. All consumers that are not required during a grid failure are connected to the grid mode branch. Consumers that should continue to be supplied during backup mode go in the backup mode branch.

If an overload occurs in the house grid because there are too many consumers in backup mode or when a backup power network is being established, the inverter tries to establish a backup power network three times before shutting down. A message on the inverter display indicates that this has happened. If this occurs, reduce the consumers and acknowledge the message on the inverter display. The inverter then tries to establish a backup power network again.

1

PLENTICORE G3

2

KOSTAL BackUp Switch (manual transfer switch), KOSTAL Auto BackUp Switch (automatic transfer switch)

3

Mains operation

4

Backup operation

5

Loads in mains operation

6

Loads in backup mode

Please note the following points