Digital inputs

INFO

Info

The settings in this menu can only be configured after logging in as the installer.

Parameter

Function

None

There is nothing connected to the digital inputs.

Active power control

For the connection of a ripple control receiver with standard switching specifications.

Detailed description in chapter Self-consumption. Active power control

Activate the distribution of ripple control signals in the house grid.

Activated:
If a ripple control receiver is connected to the inverter, the control signals of this ripple control receiver are distributed in the local LAN network by means of UDP. Other inverters can therefore also be controlled using the connected ripple control receiver.

Deactivated:
The control signals are not distributed in the local LAN network by means of UDP.

User-defined active/reactive power control

For the connection of a ripple control receiver. Unlike the standard active power control, here you can specify up to 16 settings. These are usually specified by the energy supply company.

Detailed description in chapter Self-consumption. Active power control

Activate the distribution of ripple control signals in the house grid.

Activated:
If a ripple control receiver is connected to the inverter, the control signals of this ripple control receiver are distributed in the local LAN network by means of UDP. Other inverters can therefore also be controlled using the connected ripple control receiver.

Deactivated:
The control signals are not distributed in the local LAN network by means of UDP.

External battery management

If you have activated external control via the digital I/O ports in the Battery settings menu, you can define the functions of the inputs here. Assign the desired charge or discharge power to the inputs.

Power limitation in accordance with Section 14a of the German Energy Industry Act (EnWG)

For connecting an FNN control box with standard switching specifications and additional control in accordance with Section 14a.

In accordance with Section 14a, devices which draw energy from the public grid, such as heat pumps, wallboxes or even a battery that is connected to the inverter and can be charged from the grid, can be limited by the energy supplier (power reduction). If power reduction is active, the current max. amount that can be drawn according to Section 14a is 4200 W. Ask your energy supply company what power limit you should set.

Max. rated input (W):
Here enter the power limit in accordance with Section 14a. This is the max. power with which energy may be drawn from the public grid via the inverter if the energy supplier has activated power reduction.

Activate the Distribution of ripple control signals in the house grid.

Activated:
If a ripple control receiver or FNN control box is connected to the inverter, the control signals of the FNN control box are distributed in the local LAN network by means of UDP. Other inverters can therefore also be controlled via the connected FNN control box.

Deactivated:
The control signals are not distributed in the local LAN network by means of UDP.