Technical data
Subject to technical changes. Errors excepted.
You can find current information at www.kostal-solar-electric.com.
Hybrid inverter |
|
PLENTICORE plus G2 | |||||
---|---|---|---|---|---|---|---|
Power class |
|
3.0 |
4.2 |
5.5 |
7.0 |
8.5 |
10 |
Input side (DC) |
Unit |
3.0 |
4.2 |
5.5 |
7.0 |
8.5 |
10 |
---|---|---|---|---|---|---|---|
Max. PV power (cos φ = 1) |
kWp |
4.5 |
6.3 |
8.25 |
10.5 |
12.75 |
15 |
Max. PV power per DC input |
kWp |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
Nominal DC power |
kW |
3.09 |
4.33 |
5.67 |
7.22 |
8.76 |
10.31 |
Rated input voltage (Udc,r) |
V |
570 |
570 |
570 |
570 |
570 |
570 |
Start input voltage (Udc,start) |
V |
150 |
150 |
150 |
150 |
150 |
150 |
Input voltage range (Udc,min) |
V |
120 |
120 |
120 |
120 |
120 |
120 |
Input voltage range (Udc,max) |
V |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
MPP working voltage range (Umpp,workmin) |
V |
120 7 |
120 7 |
120 7 |
120 7 |
120 7 |
120 7 |
MPP working voltage range (Umpp,workmax) |
V |
720 7 |
720 7 |
720 7 |
720 7 |
720 7 |
720 7 |
Max. working voltage (Udc,workmax) |
V |
900 |
900 |
900 |
900 |
900 |
900 |
Max. input current (idc, max) per DC input |
A |
13 |
13 |
13 |
13 |
13 |
13 |
Max. PV short-circuit current (Isc,pv) per DC input |
A |
16.25 |
16.25 |
16.25 |
16.25 |
16.25 |
16.25 |
Number of DC inputs |
|
3 |
3 |
3 |
3 |
3 |
3 |
Number of DC inputs for battery (optional) |
|
1 |
1 |
1 |
1 |
1 |
1 |
Number of independent MPP trackers |
|
3 |
3 |
3 |
3 |
3 |
3 |
Input side (DC 3 – battery input) |
Unit |
3.0 |
4.2 |
5.5 |
7.0 |
8.5 |
10 |
---|---|---|---|---|---|---|---|
Working voltage range battery input (Udc,workbatmin) |
V |
120 7 |
120 7 |
120 7 |
120 7 |
120 7 |
120 7 |
Working voltage range battery input (Udc,workbatmax) |
V |
650 |
650 |
650 |
650 |
650 |
650 |
Max. charging current/discharging current at battery input |
A |
13/13 |
13/13 |
13/13 |
13/13 |
13/13 |
13/13 |
Output side (AC) |
Unit |
3.0 |
4.2 |
5.5 |
7.0 |
8.5 |
10 |
---|---|---|---|---|---|---|---|
Rated power, cos φ = 1 (Pac,r) |
kW |
3 |
4.2 |
5.5 |
7 |
8.5 |
10 |
Output apparent power (Sac,nom, Sac,max) |
kVA |
3 |
4.2 |
5.5 |
7 |
8.5 |
10 |
Min. output voltage (Uac,min) |
V |
320 |
320 |
320 |
320 |
320 |
320 |
Max. output voltage (Uac,max) |
V |
500 |
500 |
500 |
500 |
500 |
500 |
Rated output current (Iac,r) |
A |
4.33 |
6.06 |
7.94 |
10.1 |
12.27 |
14.43 |
Max. output current (Iac,max) |
A |
4.81 |
6.74 |
8.82 |
11.23 |
13.63 |
16.04 |
Inrush current (Iinrush) |
A |
2.46 |
2.46 |
2.46 |
6.72 |
6.72 |
6.72 |
Short-circuit current (peak/RMS) |
A |
6.8/4.8 |
9.5/6.7 |
12.5/8.8 |
15.9/11.2 |
19.3/13.6 |
22.8/16.1 |
Number of feed-in phases |
|
3 |
3 |
3 |
3 |
3 |
3 |
Grid connection |
|
3N~, AC, 400 V |
3N~, AC, 400 V |
3N~, AC, 400 V |
3N~, AC, 400 V |
3N~, AC, 400 V |
3N~, AC, 400 V |
Rated frequency (fr) |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
Grid frequency (fmin/fmax) |
Hz |
47/53 |
47/53 |
47/53 |
47/53 |
47/53 |
47/53 |
Power factor setting range (cos[φ,adj]) |
|
0.8…1 |
0.8…1 |
0.8…1 |
0.8…1 |
0.8…1 |
0.8…1 |
Power factor at rated power (cos[φac,r]) |
|
1 |
1 |
1 |
1 |
1 |
1 |
Max. THD |
% |
3 |
3 |
3 |
3 |
3 |
3 |
Device properties |
Unit |
3.0 |
4.2 |
5.5 |
7.0 |
8.5 |
10 |
---|---|---|---|---|---|---|---|
Standby |
W |
7.9 |
7.9 |
7.9 |
7.9 |
7.9 |
7.9 |
Efficiency |
Unit |
3.0 |
4.2 |
5.5 |
7.0 |
8.5 |
10 |
---|---|---|---|---|---|---|---|
Max. efficiency |
% |
97.1 |
97.1 |
97.1 |
97.2 |
97.2 |
97.2 |
European efficiency |
% |
95.3 |
95.5 |
96.2 |
96.5 |
96.5 |
96.5 |
MPP adjustment efficiency |
% |
99.9 |
99.9 |
99.9 |
99.9 |
99.9 |
99.9 |
System data |
Unit |
3.0 |
4.2 |
5.5 |
7.0 |
8.5 |
10 |
---|---|---|---|---|---|---|---|
Topology: Without galvanic isolation – transformerless |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Protection class in accordance with IEC 60529 |
|
IP65 |
IP65 |
IP65 |
IP65 |
IP65 |
IP65 |
Protective class in accordance with IEC 62103 |
|
I |
I |
I |
I |
I |
I |
Overvoltage category according to IEC 60664-1 Input side (DC) 8 |
|
II |
II |
II |
II |
II |
II |
Overvoltage category according to IEC 60664-1 Output side (AC) 9 |
|
III |
III |
III |
III |
III |
III |
Degree of contamination 10 |
|
4 |
4 |
4 |
4 |
4 |
4 |
Environmental category (outdoor installation) |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Environmental category (indoor installation) |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
UV resistance |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Cable diameter of AC connection cable (min-max) |
|
8…17 |
8…17 |
8…17 |
8…17 |
8…17 |
8…17 |
Cable cross-section of AC connection cable (min-max) |
mm² |
1.5…6 |
1.5…6 |
1.5…6 |
2.5…6 |
2.5…6 |
4…6 |
Cable cross-section of PV connection cable (min-max) |
mm² |
2.5…6 |
2.5…6 |
2.5…6 |
2.5…6 |
2.5…6 |
2.5…6 |
Cable cross-section of battery connection cable (min-max) |
mm² |
4…6 |
4…6 |
4…6 |
4…6 |
4…6 |
4…6 |
Torque of screws in terminal compartment |
Nm |
2 |
2 |
2 |
2 |
2 |
2 |
Torque of screws in cover |
Nm |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
Max. fuse protection on output side according to IEC 60898-1 |
|
B16/C16 |
B16/C16 |
B16/C16 |
B16/C16 |
B16/C16 |
B25 / C25 |
Compatibility with external residual current protection devices |
|
Type A RCD |
Type A RCD |
Type A RCD |
Type A RCD |
Type A RCD |
Type A RCD |
Internal operator protection in accordance with EN 62109-2 |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Independent disconnection device according to VDE V 0126-1-1 11 |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Electronic DC disconnection device integrated |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Reverse polarity protection, DC side |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Height/width/depth |
mm |
563 / 405 / 233 |
563 / 405 / 233 |
563 / 405 / 233 |
563 / 405 / 233 |
563 / 405 / 233 |
563 / 405 / 233 |
Weight |
kg |
19.6 |
19.6 |
19.6 |
21.6 |
21.6 |
21.6 |
Cooling principle – regulated fans |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Max. air throughput |
m³/h |
184 |
184 |
184 |
184 |
184 |
184 |
Noise emission (typical) 12 |
dB(A) |
39 |
39 |
39 |
39 |
39 |
39 |
Ambient temperature |
°C |
-20 ... 60 |
-20 ... 60 |
-20 ... 60 |
-20 ... 60 |
-20 ... 60 |
-20 ... 60 |
Max. operating altitude above sea level |
m |
2000 |
2000 |
2000 |
2000 |
2000 |
2000 |
Relative humidity |
% |
4 … 100 |
4 … 100 |
4 … 100 |
4 … 100 |
4 … 100 |
4 … 100 |
Connection technology, DC side – SUNCLIX plug |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Connection technology, AC side – Spring-type terminal strip |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Connection technology interfaces – Push-in terminals |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Interfaces |
Unit |
3.0 |
4.2 |
5.5 |
7.0 |
8.5 |
10 |
---|---|---|---|---|---|---|---|
Ethernet LAN (RJ45/100 Mbit/s) |
|
2 |
2 |
2 |
2 |
2 |
2 |
Wifi (2.4 GHz [802.11 b/g/n]) |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
RS485 / CAN (for battery communication) |
|
1 |
1 |
1 |
1 |
1 |
1 |
Energy meter connection for collecting energy data (Modbus RTU) |
|
1 |
1 |
1 |
1 |
1 |
1 |
Digital inputs (e.g. for ripple control receiver or external battery control, CEI, OVP evaluation) |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Digital outputs (e.g. for self-consumption control) |
|
4 (24 V, 100 mA) |
4 (24 V, 100 mA) |
4 (24 V, 100 mA) |
4 (24 V, 100 mA) |
4 (24 V, 100 mA) |
4 (24 V, 100 mA) |
Webserver (user interface) |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Directives / Certification |
---|
CE, GS, CEI 0-21, C10/11, EN 62109-1, EN 62109-2, EN 60529, EN 50438*, EN 50549-1*, NA/EEA, G98, G99, EIFS2018, IEC 61727, IEC 62116, RD 1699, RD 647, RFG, TF3.3.1, TOR generators, UNE 206006, UNE 206007-1, VDE 0126-1-1, VDE-AR-N 4105, VJV2018 (* does not apply to all national appendices) |