Overview of Smart Communication Board (SCB)
Item |
Designation |
Terminal |
Pin |
Explanation |
---|---|---|---|---|
1 |
Not used |
X603 |
|
- |
2 |
Digital switched outputs |
X1401 |
1–2 |
Potential-free switched outputs OUT 1 (NO or NC contact) |
3–4 |
Potential-free switched outputs OUT 2 (NO or NC contact) | |||
3 |
Digital switched outputs |
X1402 |
5–6 |
Potential-free switched outputs OUT 3 (NO or NC contact) |
7–8 |
Potential-free switched outputs OUT 4 (NO or NC contact) | |||
4 |
Digital interface terminal for ripple control receiver/external battery control |
X401 |
1 |
REF (+12 to 14 V supply voltage) |
2 |
Input 1 | |||
3 |
Input 2 | |||
4 |
Input 3 | |||
5 |
Input 4 | |||
6 |
COM (0 V ground) | |||
5 |
Terminal for ripple control receiver CEI for Italy |
X403 |
1 |
common ref connection |
2 |
commando locale connection | |||
3 |
signale esterno connection | |||
6 |
Battery communication terminal |
X601 |
1 |
VDD (+12 to 14 V supply voltage) |
2 |
CANopen High interface (data +) | |||
3 |
CANopen Low interface (data -) | |||
4 |
RS485 interface B | |||
5 |
RS485 interface A | |||
6 |
GND (0 V ground) | |||
7 |
SPD monitor input connection (evaluating external overvoltage protection device) |
X402 |
1 |
Not used |
2 | ||||
3 | ||||
4 | ||||
5 |
PLC monitor | |||
6 |
GND (0 V ground) | |||
8 |
Terminal for energy meter (Modbus RTU) |
X452 |
1 |
Interface A RS485/Modbus RTU |
2 |
Interface B RS485/Modbus RTU | |||
3 |
GND | |||
9 |
USB 2.0 interface |
X171 |
1 |
USB 2.0 max. 500 mA (for service purposes) |
10 |
Ethernet connection (RJ45) |
X207 |
1 |
RJ45 max. 100 Mbit (LAN connection for connection e.g. to a router or for other devices, e.g. inverter, KSEM) |
11 |
X206 |
1 |