Configure evaluation of external overvoltage protection in the Webserver
If a surge protection device (SPD) has been installed in your system, you can connect the potential-free signal contact of the surge protection module to terminal X402 of the inverter and monitor the correct functioning of the module. In the event of a fault, the inverter outputs an event code and reports this to the KOSTAL Solar Portal.
You can also set up a switching output for event reporting Set up switched output for reporting events.
1 | Connection terminal X402 Smart Communication Board (SCB |
2 | Surge protection devices (SPD) for AC and DC side |
3 | Control cable from SPD to inverter |
1 | Connection terminal X402 Smart Communication Board (SCB |
2 | Surge protection devices (SPD) for AC and DC side |
3 | Control cable from SPD to inverter |
Activating evaluation of the external signal from the surge arrester
INFO

The IP address can be read on the inverter's display.
- Open the web server. To do this, enter the inverter IP address in the address bar of your internet browser and confirm with ENTER.
- The web server page opens.
- Log in to the web server as an installer.
- Select the menu item Service > General > Surge protection.
- The Surge Protection page opens.
- Activatethe evaluation of the external signal (terminal X402).
- Under The signal is connected as, select the function Normally Open (NO) or Normally Closed (NC).
- Click on the Save button.
- The function is now active.