External battery control via digital inputs

1

External energy management system (e.g. energy supply company)

2

External control box

3

Inverter control electronics

If external battery control via digital inputs is selected, the inverter receives the control signals for charging and discharging the connected battery via the digital inputs of the Smart Communication Board (SCB).

It is important that the digital inputs are configured accordingly in the web server.

The internal energy management remains active, but is overridden by the external specifications for charging and discharging power.

The following commands are possible:

The specifications of the external supplier must be observed.

Activate external battery control via digital inputs

  1. Connect the inverter and computer. Connecting methods between inverter/computer
  2. Start the internet browser.
  3. Open the web server. To do this, enter the IP address of the inverter to which the external control box is connected in the address bar of the browser and confirm with ENTER.
  4. INFO

    Info

    The IP address can be read on the inverter's display.

  5. The web server page will open.
  6. Log in to the web server as an installer.
  7. Select the menu item Battery > Battery settings.
  8. The Battery Settings page opens.
  9. Under Battery control, select the External via digital I/O function.
  10. Click on the Save button.
  1. The function is now active.

Configuring the digital inputs

  1. Select the menu item Service > General > Digital Inputs.
  2. The Digital Inputs page opens.
  3. Under Operating mode, select the External battery management function.
  4. Click on the Save button.
  1. The function is now active.