Routing AC supply cable

DANGER

danger

Risk of fire due to overload

If the line circuit breaker and supply cable are not suitably designed, there is a risk of fire due to cable overload.

  • Design the line circuit breaker and supply cable in accordance with the device’s technical data.

INFO

Info

If mounting on the wall, the position of the supply cable must be planned using the drilling template or illustration supplied. Cable inlets are located on the rear, bottom and top.

  1. Route the supply cable to the desired location.
  2. Observe the permissible bending radius when routing the supply cable. Approx. 30 cm of cable is required for the supply cable inside the wallbox.
  3. Design the supply cable in accordance with the wallbox’s technical data (Technical data) and observe the following local conditions:
    - Cable length, cross-section and cable type
    - Type of routing and cable coverings

INFO

Info

Installing the wallbox in a supply network in which sources of interference (e.g. a frequency inverter) are operated may result in malfunctions or termination of the charging process.

Residual current device

The required residual current device must be located in the house installation (in accordance with IEC 60364-7-722 [in Germany in accordance with DIN VDE 0100-722]).

Line circuit breaker