System start
Before starting the system, ensure that all PE and power cables, as well as communication cables, are properly connected.
1 | Line circuit breaker/break switch |
2 | On/Off button |
Follow the steps to start the system:
- Switch on the battery’s line circuit breaker/break switch.
- Press the On/Off button to start the system.
- The battery system is running.
Configuration after system start-up
By default, First Tower and Last Tower are enabled on delivery.
If only one tower is used, First Tower and Last Tower must be activated simultaneously on that tower.
In a parallel connection of several towers, First Tower must only be activated on the tower connected to the inverter. First Tower and Last Tower must be deactivated on all others. Last Tower must only be activated on the last tower. Connecting towers in parallel