Inverter settings

Time setting

Explanation

Synchronize inverter time

Synchronize the time of the inverter with the time of the smartphone.

The following menu items can be used to set the parameters in the inverter, which are specified by the grid operator. Parameters may only be changed on the inverter by qualified electricians who are familiar with the system and at the request of the grid operator. Inappropriate settings can be hazardous and lead to injury or even death of the user or third parties. Material damage to the device and other equipment can also occur.

 

Grid settings

Explanation

Frequency monitoring of level 1 activated

Activate/deactivate frequency monitoring level 1

PV string monitoring

If the function is activated, one value per PV string is displayed on the home page.

In addition, an event is output if the polarity of the PV string is reversed.

Grid guideline

Select grid guideline (e.g. VDE-AR-N 4105)

Start up time (s)

Start-up waiting time after switching on the inverter

Start up time following grid error (s)

Start-up time following inverter grid error

Power gradient (%/min)

Power gradient after switching on the inverter

Power gradient following grid error (%/min)

Power gradient after grid error of the inverter

Overfrequency limit value x (Hz)

Set overfrequency limit threshold value

Underfrequency limit value x (Hz)

Set underfrequency protection threshold value

Overvoltage limit value x (V)

Set overvoltage protection limit value

Undervoltage limit value x (V)

Set undervoltage protection limit value

Overfrequency switch-off time x time (s)

Set overfrequency switch-off time

Underfrequency switch-off time x time (s)

Set underfrequency shut-off time

Overvoltage switch-off time x time (s)

Set overvoltage switch-off time

Undervoltage switch-off time x time (s)

Set undervoltage switch-off time

Max. grid start voltage (V)

If the supply voltage is higher than the upper limit of the reconnection voltage after the inverter has been shut down for protection due to a fault, the inverter may not be reconnected to the grid.

Min. grid start voltage (V)

After the inverter is shut down for protection due to a fault, if the supply voltage is lower than the lower limit of the reconnection voltage, the inverter may not be reconnected to the grid.

Max. grid start frequency (Hz)

After the inverter is shut down for protection due to a fault, if the grid frequency is higher than the upper limit of the reconnection frequency, the inverter may not be reconnected to the grid.

Min. grid start frequency (Hz)

After the inverter is shut down for protection due to a fault, if the grid frequency is lower than the lower limit of the reconnection frequency, the inverter may not be reconnected to the grid.

Moving average

Set 10 minutes of average overvoltage value

 

Power adaptation/
controls

Explanation

Active power control

Active power control

 

P(U) regulation

Parameter of the P(U) curve, which reduces the active power if the output voltage exceeds a certain value

P(F) regulation

Parameter of the P(f) curve, which decreases the active power during overfrequency or increases the active power during underfrequency

Power gradient (%/s)

Set the power gradient. The power gradient indicates how quickly the power is to be increased or decreased.

Maximum feed-in capacity (W)

Set the inverter's maximum active power

Maximum active power (%)

Setting for maximum output power of the inverter

Reactive power control

Reactive power control

 

Settling time of reactive power

Specifies the reactive power settling time (3 Tao, PT-1 behaviour)

Reactive power mode

Specifies the reactive power control mode.

Configure settings according to the power supply company for reactive power control.

Energy management

Power limitation

 

Power limitation function

Deactivated: No energy meter connected to the inverter.

KSEM: A KOSTAL Smart Energy Meter is connected to the inverter.

Sensor position

Installation position of energy meter (grid connection point or consumer) Connecting the KOSTAL Smart Energy Meter

Modbus address of energy meter

Energy meter Modbus address

Limitation of the active power to (W)

Set up power limitation

IP address of energy meter

Energy meter IP address

L1-3 grid power

Displays the grid power at the individual phases

Total energy

Shows the energy supply from the public grid

Total feed-in energy

Shows the feed-in into the public grid

L1-3 consumer power

Shows the consumer power at the individual phases

Total consumption

Shows the total consumption

L1-3 inverter output

Shows the inverter output at on the individual phases

Total inverter output

Shows the total energy generated by the inverter

Ripple control receiver

Ripple control receiver control

 

Activate ripple control receiver

Activate/deactivate ripple control receiver function Connecting ripple control receiver

RCR active power (%)

Set active power value for ripple control receiver

RCR reactive power

Set reactive power value or power factor cos phi for ripple control receiver

 

Other settings

Explanation

Isolated network detection

Activate/deactivate isolated network detection.

Ensures that the inverter does not switch on or off in the event of supply voltage errors.

Residual current monitoring

Activate/deactivate residual current monitoring.

When the function is enabled, the inverter detects the array fault current.

Compatibility of type A RCD

If this function has been activated, type A RCDs can be used as residual current protection equipment. In such cases, the inverter shuts down when the residual current becomes incompatible with a type A RCD.

If the function is deactivated, a type B RCD must be used as residual current protection equipment if an RCD is stipulated.

Shadow management

If PV strings are in partial shading, the PV string affected no longer achieves its optimum performance. If shadow management is activated, the inverter adapts the MPP tracker in such a way that it can operate at maximum possible performance.

Shadow management interval time (s)

Set the interval of the MPP tracker sampling rate

Insulation resistance (kOhm)

If the value established for insulation resistance is less than the preset value, the inverter is not connected to the grid

Leakage current limit (mA)

Limit value for leakage current detection. If the value established is higher than the preset value, the inverter will shut down.

Limit for unbalanced voltage (%)

Set threshold value for supply voltage unbalance

Dynamic grid support (FRT)

Dynamic grid support (FRT = Fault Ride Through)

 

Positive sequence K factor

Settings for uninterrupted cycling through grid faults

FRT (Fault Ride Through)

Negative sequence K factor

Monitoring of supply voltage

Undervoltage ride through (V) UVRT

Overvoltage ride through (V) OVRT

Grid support mode

Limited grid support (%)

Irregular voltage change (%)

Overvoltage protection monitoring

Activate/deactivate monitoring of the internal overvoltage protection modules (SPD - Surge Protective Device).