Electrical connection

Perform the following steps:

  1. De-energise the house grid.
  2. DANGER

    danger

    Risk of death due to electrical shock and discharge!

    De-energise device and secure against being switched on again. De-energising the inverter

  3. Fit ripple control receiver in control cabinet or power distributor.
  4. Correctly route the communication cable from the inverter to the control cabinet and connect to the ripple control receiver following the wiring diagram provided by the manufacturer.
  5. Connect communication cable in inverter to terminal for ripple control receiver (torque: 0.2 Nm).
  6. Once the inverter has undergone initial commissioning, the ripple control receiver must still be configured in the Webserver. The function that forwards the ripple control receiver's signals (distribution of broadcast control signals) to other inverters in the same house network can also be activated. Activating active power control
  1. The ripple control receiver is connected.

More information about configuration Active power control